MIB Objects
Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path Trap LevelTrap
trapBypassFrequencyOutOfRange
Bypass under or over frequency
UPS.PowerConverter.Input[2].PresentStatus.FrequencyOutOfRange = 1
5 2
trapBypassFrequencyOutOfRangeOk
Bypass under or over frequency ok
UPS.PowerConverter.Input[2].PresentStatus.FrequencyOutOfRange = 0
6 1
trapOnBuck
On Buck / Input Voltage Reducer
UPS.PowerConverter.Input[1].PresentStatus.Buck = 1
7 1
trapReturnFromBuck
Return from Buck
UPS.PowerConverter.Input[1].PresentStatus.Buck = 0
8 1
trapOnBoost
On Boost / Input Voltage Booster
UPS.PowerConverter.Input[1].PresentStatus.Boost = 1
9 1
trapReturnFromBoost
Return from Boost
UPS.PowerConverter.Input[1].PresentStatus.Boost = 0
10 1
trapInputOverVoltage
Input AC over voltage
UPS.PowerConverter.Input[1].PresentStatus.VoltageTooHigh = 1
11 2
trapInputOverVoltageOk
Input AC over voltage ok
UPS.PowerConverter.Input[1].PresentStatus.VoltageTooHigh = 0
12 1
trapInputUnderVoltage
Input AC under voltage
UPS.PowerConverter.Input[1].PresentStatus.VoltageTooLow = 1
13 2
trapInputUnderVoltageOk
Input AC under voltage ok
UPS.PowerConverter.Input[1].PresentStatus.VoltageTooLow = 0
14 1
trapInputFrequencyOutOfRange
Input under or over frequency
UPS.PowerConverter.Input[1].PresentStatus.FrequencyOutOfRange = 1
15 2