USER’S GUIDE
Managed Rack PDU
176
Customizing. You must customize the file before you export it.
1. Use a text editor to customize the file.
Section headings, keywords, and pre-defined values are not case-sensitive, but
string values that you define are case-sensitive.
Use adjacent quotation marks to indicate no value. For example, LinkURL1=""
indicates that the URL is intentionally undefined.
Enclose in quotation marks any values that contain leading or trailing spaces or
are already enclosed in quotation marks.
To export scheduled events, configure the values directly in the .ini file.
To export a system time with the greatest accuracy, if the receiving Rack PDUs
can access a Network Time Protocol server, configure enabled for NTPEnable:
NTPEnable=enabled
Alternatively, reduce transmission time by exporting the [SystemDate/Time]
section as a separate .ini file.
To add comments, start each comment line with a semicolon (;).
2. Copy the customized file to another file name in the same folder:
The file name can have up to 64 characters and must have the .ini suffix.
Retain the original customized file for future use. The file that you retain is the
only record of your comments.