USER’S GUIDE
Managed Rack PDU
17
Local access to the command line interface
For local access, use a computer that connects to the Rack PDU through the serial port
to access the command line interface:
1. Select a serial port at the computer and disable any service that uses that port.
2. Connect the supplied serial cable from the selected serial port on the computer to
the serial port on the Rack PDU.
3. Run a terminal program (e.g., HyperTerminal) and configure the selected port for
9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control.
4. Press
ENTER, and at the prompts, enter your user name and password.