cfgChassisPowerCapFPercent (Read/Write)
Description Indicates the power consumption limit as a percentage.
The percentage is computed mathematically as the
minimum power + (percent * (maximum power - minimum
power)). Use cfgChassisPowerCapFPercent when power
consumption is to be changed regardless of whether
server throttling is required.
Legal Values 16 - 100
Default 100
cfgChassisRedundancyPolicy (Read/Write)
Description Sets the redundancy policy of the chassis.
Legal Values
0 (no redundancy)
1 (AC redundancy)
2 (power supply redundancy)
Default 0 (no redundancy)
cfgChassisDynamicPSUEngagementEnable (Read/Write)
Description Enables or disables dynamic engagement.
Legal Values
0 (disabled)
1 (enabled)
Default 0 (disabled)
cfgChassisAllow110VACOperation (Read/Write)
Description Enables or disables normal chassis power allocations
when any power supply unit is connected to 110V AC
service. If disabled and 110V power supplies are detected,
all subsequent server power allocation requests are
denied. In this mode additional servers cannot be
powered on, regardless of server priority.
Legal Values
0 (disabled)
1 (enabled)
Default 0 (disabled)