Configuration 61
Configure Parameters for Other Dell ULNMs
Other Dell ULNM's will discover this Dell ULNM through a network scan.
From these other Dell ULNMs, configure the parameters in Setting > Shutdown > Configuration.
The main parameters are:
Power Source (indicate the IP address of Dell ULNM#1 that is the Shutdown Controller)
•Load Segment
Login and Password (You must use “admin” account)
Click Save when you enter all parameters.
Now this Dell ULNM is registered in the “Notified Applications” view of the Shutdown Controller (see
“Notified Applications View” on page 62).
Example with 3 computers
NOTE: Refer to the Shutdown Use Cases for Architecture #3 on page 44.
A UPS is locally connected (through USB) to computer 1 hosting Dell ULNM #1 (Shutdown Controller
role):
The Dell ULNM #1 automatically detects its UPS.
You must activate the “Shutdown Controller” feature for Dell ULNM #1.
In Dell ULNM #2 interface, you must indicate the IP address of Dell ULNM #1 computer, the load
segment, and Dell ULNM #1 Login and Password.
In Dell ULNM #3 interface, you must indicate the IP address of Dell ULNM #1 computer, the load
segment, and Dell ULNM #1 Login /Password.
Dell ULNM #1 will forward Shutdown alarms to remote Dell ULNM instances (Dell ULNM #2 and
Dell ULNM #3).
As a consequence, the three servers powered by this UPS are protected.
Figure 45 provides a corresponding power flow view where one UPS powers three single-feed servers:
Figure 45. Power Flow View
0120_3-Dell ULNM UG.book Page 61 Saturday, November 2, 2013 5:34 PM