Dell Chassis Management Controller Version 1.0 for PowerEdge VRTX Guide de l'utilisateur Page 639

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 931
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 638
Detailed
Description
One of more fans have failed or have been removed or a configuration change occurred which
requires additional fans.
Recommended
Response Action
Remove and re-install failed fans or install additional fans.
Category System Health
SubCategory RDU = Redundancy
Severity Severity 1 (Critical)
Trap/EventID FALSE
LCD Message No LCD message display defined.
Initial Default. FALSE
Filter
Visibility
IPMI Alert SNMP
Alert
Email
Alert
LC Log LCD Power Off Power
Cycle
Reset
FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE
RDU0011
Message The power supplies are redundant.
Detailed
Description
None
Recommended
Response Action
No response action is required.
Category System Health
SubCategory RDU = Redundancy
Severity Severity 3 (Informational)
Trap/EventID 2475
LCD Message No LCD message display defined.
Initial Default. LC Log
Filter
Visibility
IPMI Alert SNMP
Alert
Email
Alert
LC Log LCD Power Off Power
Cycle
Reset
TRUE FALSE TRUE TRUE TRUE FALSE FALSE FALSE FALSE
RDU0012
Message Power supply redundancy is lost.
Detailed
Description
The current power operational mode is non-redundant because of a power supply exception, a
power supply inventory change, or a system power inventory change. The system was
previously operating in a power redundant mode.